Draw out Type 12kv 630A Vacuum Circuit Breaker with Insulated Cylinder

Draw out Type 12kv 630A Vacuum Circuit Breaker with Insulated Cylinder

Description
VS1 (ZN63A) -12(24)M sequence indoor high voltage vacuum circuit breaker is geared up with Modular system, which has a far more secure integrated performance. This VCB is utilized for AC 12kV, 50Hz indoor high voltage switchgear, broadly relevant to electrical power stations, substations, and industrial and mining enterprises to manage or safety electrical power transmission and distribution systems, specifically for the critical high altitude breaking load and regular procedure area and reputable interlock function.
The VCB can be used for really recurrent operation area, equipped with KYN28A-12 handcart type swap cabinet, and the set variety VCB can also be used for XGN sequence switch cupboards. It conforms to Nationwide CZPT GB1984-2003, and the connected IEC requirements.
      The circuit breaker is created as a entrance-rear split charging composition, which the two can be utilised as a fixed installation unit, and also be equipped with the chassis as employed in the mounted, handcart device.

Surroundings Situation:
– Ambient temperature:-15ºC~+40ºC
– Altitude: ≤1000m
– Everyday average relative humidity: ≤95%
– Month-to-month regular relative humidity: ≤90%
– Earthquake depth: ≤8 degree 
– No hearth, explosion, serious vibration, chemical corrosion and significant pollution

CZPT Data

1 Rated voltage kV 12 (24)
2 Max. doing work voltage kV 12 (24)
3 Rated Present A 630, 1250 1600,2000
2500, 3150
2000, 2500
3150, 4000
four Rated quick-circuit breaking recent kA 20/twenty five 31.fifty forty
five Rated brief-circuit closing existing (peak) kA 50/63 eighty one hundred
6 Rated peak withstand existing kA 50/63 80 a hundred
7 4s rated brief-circuit stand up to existing kA twenty/twenty five 31.50 40
8 Nos. of rated short-circuit breaking recent Instances 50 (30 over 40kA)
nine Rated working sequence   -.3s-CO-180s-CO/
-180s-CO-180s-CO(Above 40KA)
10 Rated lightning impulse stand up to voltage kV 75 (one hundred twenty five)
eleven 1min power frequency face up to voltage kV forty two (sixty five)
12 Mechanical existence Occasions 10000
thirteen Speak to open distance mm 10 (twelve)±1
14 Get in touch with Over-vacation (Size of spring compression) mm three.5±0.5
fifteen Rated swap-on/off functioning voltage V AC110/220,DC110/220
16 Tripping time Max. running voltage s ≤0.05
Min. working voltage ≤0.08
17 Closing time s .one
eighteen Motor rated electrical power W 70 (previously mentioned 40kA: 100W)
19 Typical closing speed m/s .five-.eight
twenty Typical opening pace m/s .9-one.two
21 Contact closing bounce time ms ≤2
22 A few section make contact with closing opening asynchrony ms ≤2
23 The primary circuit resistance every phase μΩ 630A≤50, 1250A≤50, 1600A≤40
24 Allowed consumpted thickness of contacts mm 3

 